VEGA FIBERTRAC 31 Foundation Fieldbus User Manual

Page 64

Advertising
background image

64

11 Supplement

FIBERTRAC 31 • Foundation Fieldbus

41780-EN-131119

Output variable - Level measurement
Output

Ʋ Signal

digital output signal, Foundation Fieldbus protocol

Ʋ Physical layer

according to IEC 61158-2

Damping (63 % of the input variable)

0 … 999 s, adjustable

Channel Numbers

Ʋ Channel 1

Process value (level)

Ʋ Channel 8

Electronics temperature

Ʋ Channel 9

Pulse rate

Transmission rate

31.25 Kbit/s

Current value

10 mA, ±0.5 mA

Resolution, digital

> 0.1 mm (0.004 in)

Output variable - Level detection
Output

Ʋ Signal

digital output signal, Foundation Fieldbus protocol

Ʋ Physical layer

according to IEC 61158-2

Damping (63 % of the input variable)

0 … 999 s, adjustable

Channel Numbers

Ʋ Channel 1

Process value (switching status)

Ʋ Channel 8

Electronics temperature

Ʋ Channel 9

Pulse rate

Transmission rate

31.25 Kbit/s

Current value

10 mA, ±0.5 mA

Resolution, digital

> 0.1 mm (0.004 in)

Relay output
Output

Relay output (SPDT), floating spdt

Switching voltage

Ʋ Min.

10 mV

Ʋ Max.

253 V AC, 253 V DC

Switching current

Ʋ Min.

10 µA

Ʋ Max.

3 A AC, 1 A DC

Breaking capacity

Ʋ Min.

50 mW

Ʋ Max.

750 VA AC, 40 W DC
If inductive loads or stronger currents are switched

through, the gold plating on the relay contact surface will

be permanently damaged. The contact is then no longer

suitable for switching low-level signal circuits.

Contact material (relay contacts)

AgNi or AgSnO and Au plated

Advertising