6 Set up with the display and adjustment module

FIBERTRAC 31 • Foundation Fieldbus

41780-EN-131119

You thus get the min. pulse rate (ct/s) for the "covered" adjustment.
Enter the requested pulse rate manually or let the rate be determined

by FIBERTRAC 31. Automatic determination of the pulse rate should

be given preference.

You can enter the adjustment point (ct/s) manually.

You can let the adjustment point be determined by FIBERTRAC 31.

This menu item appears only if you have selected under adjustment

mode (setup/adjustment mode) the "Two-point adjustment".
In this menu item you can set the max. pulse rate (ct/s) at which the

sensor should switch over.
Empty the vessel until the FIBERTRAC 31 is uncovered.
You thus get the max. pulse rate (ct/s) for the "uncovered" adjustment.
Enter the requested pulse rate manually or let the rate be determined

by FIBERTRAC 31. Automatic determination of the pulse rate should

be given preference.

You can enter the adjustment point (ct/s) manually.

You can let the adjustment point be determined by FIBERTRAC 31.

In this menu item you can select which mode the sensor should oper-

ate in.
You can choose between overfill and dry run protection.
The relay outputs of the sensor react accordingly.

Adjustment "uncovered"

(two-point adjustment)

Setup - Relay