3 modbus register, Protocol description, Parameters for the bus communication – VEGA VEGAFLEX 86 Modbus and Levelmaster protocol Coax probe User Manual

Page 72: General configuration of the host, Holding register

Advertising
background image

72

11 Supplement

VEGAFLEX 86 • Modbus and Levelmaster protocol

42288-EN-130314

Protocol description

The VEGAFLEX 86 is suitable for connection to the following RTUs with Modbus RTU or ASCII

protocol.

RTU

Protocol

ABB Totalflow

Modbus RTU, ASCII

Bristol ControlWaveMicro

Modbus RTU, ASCII

Fisher ROC

Modbus RTU, ASCII

ScadaPack

Modbus RTU, ASCII

Thermo Electron Autopilot

Modbus RTU, ASCII

Parameters for the bus communication

The VEGAFLEX 86 is preset with the default values:

Parameter

Configurable Values

Default Value

Baud Rate

1200, 2400, 4800, 9600, 19200

9600

Start Bits

1

1

Data Bits

7, 8

8

Parity

None, Odd, Even

None

Stop Bits

1, 2

1

Address range Modbus

1 … 255

246

Start bits and data bits cannot be modified.

General configuration of the host

The data exchange with status and variables between field device and host is carried out via

register. For this, a configuration in the host is required. Floating point numbers with short prevision

(4 bytes) according to IEEE 754 are transmitted with individually selectable order of the data bytes

(byte transmission order). This "Byte transmission order" is determined in the parameter "Format

Code". Hence the RTU knows the registers of the VEGAFLEX 86 which must be contacted for the

variables and status information.

Format Code

Byte transmission order

0

ABCD

1

CDAB

2

DCBA

3

BADC

11.3 Modbus register

Holding Register

The Holding registers consist of 16 bit. They can be read and written. Before each command, the

address (1 byte), after each command, a CRC (2 byte) is sent.

Register Name Register Num-

ber

Type

Configurable

Values

Default Value

Unit

Address

200

Word

1 … 255

246

-

Advertising