11 Supplement
VEGAFLEX 86 • Modbus and Levelmaster protocol
42288-EN-130314
Thermo Electron Autopilot
Wiring plan
+
+
power supply
MODBUS
D0
D1
IS GND
USB
1
2
3
13
45
2o
ff
on
( )
(
)
(-)
(-)
+8
+30 Vdc
to
GND
2
1
Rx -
Rx+
Fig. 40: Connection of VEGAFLEX 86 to RTU Thermo Electron Autopilot
1 VEGAFLEX 86
2 RTU Thermo Electron Autopilot
3 Voltage supply
Parameter
Parameter
Value
Baud Rate
9600
Floating Point Format Code
0
RTU Data Type
IEE Fit 2R
Input Register Base Number
0
The basic number of the input registers is always added to the input register address of VEGAFLEX
86.
Address 1300 must hence be entered as register address for 1300 for RTU Thermo Electron Auto-
pilot.