6 configuration of typical modbus hosts, Error codes, Fisher roc 809 – VEGA VEGAFLEX 86 Modbus and Levelmaster protocol Coax probe User Manual

Page 81: Wiring plan, Parameter, 11 supplement

Advertising
background image

81

11 Supplement

VEGAFLEX 86 • Modbus and Levelmaster protocol

42288-EN-130314

Response:

Parameter

Length

Code/Data

Report Receive to Transmit Delay

7 characters ASCII

UuuRmmm
mmm = milliseconds (50 up to 250),

default = 127 ms

Error codes

Error Code

Name

EE-Error

Error While Storing Data in EEPROM

FR-Error

Erorr in Frame (too short, too long, wrong data)

LV-Error

Value out of limits

11.6 Configuration of typical Modbus hosts

Fisher ROC 809

Wiring plan

+

+

power supply

MODBUS

D0

D1

IS GND

USB

B

COM

Z

Y

A

(Rx/Tx -)

(Rx/Tx +)

1

2

3

13

45

2o

ff

on

( )

(

)

(-)

(-)

+8

+30 Vdc

to

GND

Fig. 38: Connection of VEGAFLEX 86 to RTU Fisher ROC 809
1 VEGAFLEX 86

2 RTU Fisher ROC 809

3 Voltage supply

Parameter

Parameter

Value

Baud Rate

9600

Floating Point Format Code

0

RTU Data Type

Conversion Code 66

Input Register Base Number

0

Advertising