7 dimensions, Scadapack, Wiring plan – VEGA VEGAFLEX 86 Modbus and Levelmaster protocol Coax probe User Manual
Page 85: Parameter, 11 supplement
85
11 Supplement
VEGAFLEX 86 • Modbus and Levelmaster protocol
42288-EN-130314
ScadaPack
Wiring plan
+
+
power supply
MODBUS
D0
D1
IS GND
USB
1
3
2
13
45
5
2
1
3
4
9
6
7
8
2o
ff
on
( )
(
)
(-)
(-)
+8
+30 Vdc
to
GND
COM Part 3 (C3)
RS485
TXD-
TXD+
GND
Fig. 42: Connection of VEGAFLEX 86 to RTU ScadaPack
1 VEGAFLEX 86
2 RTU ScadaPack
3 Voltage supply
Parameter
Parameter
Value
Baud Rate
9600
Floating Point Format Code
0
RTU Data Type
Floating Point
Input Register Base Number
30001
The basic number of the input registers is always added to the input register address of VEGAFLEX
86.
Address 31303 must hence be entered as register address for 1302 for RTU ScadaPack.