6 Setup

VEGASWING 66 • - two-wire

43758-EN-130322

6.2 Adjustment elements

4

1

5

3

2

6

Z

Fig. 14: Electronics module - Two-wire output
1 Signal lamp - red (LED)

2 Signal lamp - yellow (LED)

3 Signal lamp - green (LED)

4 DIL switch for mode adjustment

5 DIL switch for sensitivity adjustment

6 Test key

The instrument monitors the vibrating frequency, electronics tempera-

ture and internal instrument functions.

Red LED lights = fault

Reaktion on the output

Control lamp for indication of the switching status
With the mode adjustment (4), the switching condition and hence the

function of the signal lamp can be changed.

Yellow LED lights = 8 mA

Yellow LED off = 16 mA

Green LED lights = operating voltage on

With the mode adjustment (min./max.) you can determine the output

current.

Control lamp (1) - fault

indication (red)

Signal lamp (2) - Switch-

ing condition (yellow)

Signal lamp (3) - Operat-

ing condition (green)

Mode adjustment (4)

Advertising