6 Setup

VEGASWING 66 • - two-wire

43758-EN-130322

2 Dismounting of the sensor and immersion in the original

product

You can dismount the sensor for test purposes and check its proper

functioning by immersing it in the original product.
3 Short interruption of the supply line to the sensor

The recurring function test according to IEC 61508 can be carried

out through a short interruption (> 2 seconds) of the supply line to the

sensor. This starts a test sequence.
The correctness of the subsequent switching conditions on the indi-

cations of the SPLC must be monitored. The sensor must neither be

dismounted nor triggered by filling the vessel.
You can carry out the function test with the outputted current values

also directly via a safety PLC or a process control system.
4 Pushing the test key on the signal conditioning instrument

A test key is lowered in the front plate of the signal conditioning instru-

ment. Push the test key for > 2 seconds with a suitable object. Hence

a test is started. Hence the correctness of the subsequent switching

conditions must be monitored via the two LEDs on the signal condi-

tioning instrument as well as the connected facilities. The sensor must

neither be dismounted, nor controlled by filling the vessel.

This test is valid if you cannot change the vessel filling or cannot

dismount the sensor.
The recurring function test according to IEC 61508 can be carried out

by pushing the test key on a respective signal conditioning instrument

or briefly (> 2 seconds) interrupting the supply line to the sensor.
The correctness of the subsequent switching conditions must be

monitored via the two LEDs on the signal conditioning instrument as

well as the connected devices. The sensor must neither be dismount-

ed nor triggered by filling the vessel.
This applies for VEGASWING 66 with two-wire electronics module.
You can carry out the function test with the outputted current values

also directly via a safety PLC or a process control system.
A function test can be carried out with measurement setups in con-

junction with the two-wire electronics module.
If you are using a signal conditioning instrument of type VEGATOR for

this purpose, you can also carry out the test with the integrated test

key. The test key is recessed in the front plate of the signal condi-

tioning insturment. Push the test key for > 2 seconds with a suitable

object (screwdriver, pen, etc.).
When the VEGASWING 66 is connected to a processing system or

an SPLC, you have to interrupt the connection cable to the sensor for

> 2 seconds. The switching delay must be set to 0.5 s.
After releasing the test key or interrupting the connection cable to the

sensor, the complete measuring system can be checked on correct

function. The following operating conditions are simulated during the

test:

Fault message

Test without filling or

dismounting the sensor

(3, 4)