4 parameter adjustment - extended adjustment – VEGA VEGABAR 81 HART and accumulator pack - Operating Instructions User Manual

Page 24

Advertising
background image

24

6 Set up with the display and adjustment module

VEGABAR 81 • HART and accumulator pack

45026-EN-131107

4. Position correction

In this menu item you compensate the influence of the installation

position of the instrument (offset) to the measured value.
5. zero adjustment

In this menu item you carry out the zero adjustment for the processs

pressure.
Enter the respective pressure value for 0 %.
6. span adjustment

In this menu item you carry out the span adjustment for the processs

pressure
Enter the respective pressure value for 100 %.

4. Position correction

In this menu item you compensate the influence of the installation

position of the instrument (offset) to the measured value.
5. Max. adjustment

In this menu item you carry out the max. adjustment for level
Enter the percentage value and the corresponding value for the max.

level.
6. Min. adjustment

In this menu item you carry out the min. adjustment for level
Enter the percentage value and the corresponding value for the min.

level.

The quick setup is hence finished.

6.4 Parameter adjustment - Extended adjustment

For technically demanding measurement loops you can carry out

extended settings in "Extended adjustment".

The main menu is divided into five sections with the following func-

tions:

Quick setup - Process

pressure measurement