6 Set up the sensor with the indicating and adjustment module

VEGAPULS 62 standpipe version • Modbus and Levelmaster protocol

41363-EN-121011

With radar sensors with standpipe antenna, the sensor length is

already preset in this menu item. When shortening the standpipe

antenna afterwards, this value must be appropriately corrected.

When a reset is carried out, all settings (with only a few exceptions)

are reset. The exceptions are: PIN, language and lighting.

The following reset functions are available:
Delivery status: Restoring the parameter settings at the time of ship-

ment from the factory incl. the order-specific settings. A created false

signal suppression, user-programmable linearization curve as well as

the measured value memory will be deleted.
Basic settings: Resetting the parameter settings incl. special and

laboratory parameters to the default values of the respective instru-

ment. A created false signal suppression, user programmable lineari-

zation curve as well as the measured value memory will be deleted.
Setup: Resetting of the parameter settings to the default values of the

respective instrument in the menu item Setup. Order-related settings

remain but are not taken over into the current parameters. User-

generated false signal suppression, user-programmed linearization

curve, measured value memory as well as event memory remain

untouched. The linearization is set to linear.
False signal suppression: Deleting a previously created false signal

suppression. The false signal suppression created in the factory

remains active.
Peak values distance: Resetting the measured min. and max. dis-

tances to the actual measured value.
Select the requested reset function [->] and confirm with [OK].
The following table shows the default values of VEGAPULS 62:

Menu section

Menu item

Default value

Setup

Measurement

loop name

Sensor

Min. adjustment

Length of the standpipe Ex factory

Damping

0.0 s

Display

Language

Like order

Displayed value

Distance

Display unit

m(d)

Scaling

0.00 %, 0 l
100.00 %, 100 l

Additional adjustments/

Probe length

Additional adjustments/

Reset