6 configuration of typical modbus hosts, 6 fisher roc 809, Wiring plan – VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) standpipe ver. Modbus and Levelmaster protocol User Manual
Page 58: Parameter
Advertising
58
11 Supplement
VEGAPULS 62 standpipe version • Modbus and Levelmaster protocol
41363-EN-121011
11.6 Configuration of typical Modbus hosts
11.6 Fisher ROC 809
Wiring plan
+
+
power supply
MODBUS
D0
D1
IS GND
USB
B
COM
Z
Y
A
(Rx/Tx -)
(Rx/Tx +)
1
2
3
13
45
2o
ff
on
( )
(
)
(-)
(-)
+8
+30 Vdc
to
GND
Fig. 26: Connection of VEGAPULS 62 to RTU Fisher ROC 809
1 VEGAPULS 62
2 RTU Fisher ROC 809
3 Voltage supply
Parameter
Parameter
Value
Baud Rate
9600
Floating Point Format Code
0
RTU Data Type
Conversion Code 66
Input Register Base Number
0
The basic number of the input registers is always added to the input register address of VEGAPULS
62.
Address 1300 must hence be entered as register address for RTU Fisher ROC 809.