6 abb total flow, Wiring plan, Parameter – VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) standpipe ver. Modbus and Levelmaster protocol User Manual
Page 59
Advertising
59
11 Supplement
VEGAPULS 62 standpipe version • Modbus and Levelmaster protocol
41363-EN-121011
11.6 ABB Total Flow
Wiring plan
+
+
power supply
MODBUS
D0
D1
IS GND
USB
1
2
13
45
2o
ff
on
( )
(
)
(-)
(-)
8
1
2
6
7
Bus +
Bus -
GND
VBAT
Fig. 27: Connection of VEGAPULS 62 to RTU ABB Total Flow
1 VEGAPULS 62
2 RTU ABB Total Flow
Parameter
Parameter
Value
Baud Rate
9600
Floating Point Format Code
0
RTU Data Type
16 Bit Modicon
Input Register Base Number
1
The basic number of the input registers is always added to the input register address of VEGAPULS
62.
Address 1303 must hence be entered as register address for 1302 for RTU ABB Total Flow.
Advertising