4 Mounting

VEGAFLEX 86 • Profibus PA

44232-EN-130910

1

2

Fig. 12: Position of the spacer or centering weight
1 Rod probe with spacer (steel)

2 Cable probe with centering weight

Note:

Measurement in a standpipe is not recommended for extremely

adhesive products.
Instructions for the measurement:

The 100 % point should not be above the upper tube connection

to the vessel

The 0 % point should not be below the lower tube connection to

the vessel

A false signal suppression with installed sensor is generally rec-

ommended to achieve maximum possible accuracy.

Instruments for a temperature range up to 280 °C or up to 450 °C

have a distance piece between process fitting and electronics hous-

ing. Ths distance piece is used for thermal decoupling of the electron-

ics against high process temperatures.
Information:

The distance piece must only be incorporated up to max. 50 mm (2 in)

in the vessel isolation. Only then, a reliable temperature decoupling is

guaranteed.

Mounting in the vessel

insulation