6 Set up with the display and adjustment module

VEGAFLEX 86 • Profibus PA

44232-EN-130910

available if adjustment is enabled in the menu "Lock/Release setup/

adjustment".

In delivery status, the PIN is "0000".

In this menu item, the internal clock of the sensor is adjusted.

With a reset, certain parameter adjustments carried out by the user

are reset.

The following reset functions are available:
Delivery status: Restoring the parameter settings at the time of ship-

ment from the factory incl. the order-specific settings. A created false

signal suppression, user-programmable linearization curve as well as

the measured value memory will be deleted.
Basic settings: Resetting of the parameter settings incl. special

parameters to the default values (presettings) of the respective instru-

ment. Any created false signal suppression or user-programmable lin-

earization curve as well as the measured value memory are deleted.
The following table shows the default values of the instrument. De-

pending on the instrument version or application, all menu items may

not be available or some may be differently assigned:

Setup

Menu item

Default value

Modified value

Block adjustment

Released

Measurement loop name

Sensor

Units

Distance unit: mm
Temperature unit: °C

Probe length

Length of the probe Ex factory

Type of medium

Liquid

Application

Level, vessel

Additional adjustments -

Date Time

Additional adjustments

- Reset