4 Mounting

VEGAFLEX 86 • 4 … 20 mA/HART two-wire

42284-EN-130612

1

2

Fig. 8: Mounting of the instrument on insulated vessels.
1 Temperature insulation

2 Ambient temperature on the housing

Vapours, superimposed gases, high pressures and temperature dif-

ferences can change the spreading speed of radar impulses.
There are two possibilities to correct these deviations.
Corrective value in the process control system

In the technical data under "Influence of superimposed gas and pres-

sure on accuracy" you can find a table with deviation values in some

typical gases or in steam.
In the control system (DCS) you can correct the measurement results

of the VEGAFLEX 86 with these values.
The prerequisite is constant temperature and pressure in the vessel.
Automatic correction via the reference distance

The VEGAFLEX 86 can be equipped optionally with a running time

correction via reference distance. The probe can carry out an auto-

matic running time correction with it.
The reference point must hence not be overfilled. The upper dead

band is hence 450 mm (17.7 in).