7 supplementary electronics, 8 switch-on phase – VEGA VEGAFLEX 86 4 … 20 mA_HART two-wire Coax probe User Manual

Page 27

Advertising
background image

27

5 Connecting to power supply

VEGAFLEX 86 • 4 … 20 mA/HART two-wire

42284-EN-130612

5.7 Supplementary electronics

You can use the supplementary electronics - second current output to

provided a second measured value.
Both current outputs are passive and need a power supply.

1

2

+

( )

(-)

I

4...20mA

I I

4...20mA

7

8

+

( )

(-)

3

1

2

Fig. 21: Connection compartment double chamber housing, supplementary

electronics - second current output
1 First current output (I) - Voltage supply and signal output (HART)

2 Second current output (II) - Voltage supply and signal output (without HART)

3 Ground terminal for connection of the cable screen

The radio module PLICSMOBILE is an external GSM/GPRS radio

unit for transmission of measured values and for remote parameter

adjustment.

1

Bus

USB

Status

Test

SIM-Card

1

2

+

( )

(-)

Fig. 22: Radio module PLICSMOBILE integrated in the connection compart-

ment
1 Voltage supply

You can find detailed information on connection in the supplementary

instructions "PLICSMOBILE GSM/GPRS radio module".

5.8 Switch-on phase

After connecting the instrument to power supply or after a voltage

recurrence, the instrument carries out a self-check for approx. 30 s:

Internal check of the electronics

Indication of the instrument type, hardware and software version,

measurement loop name on the display or PC

Indication of the status message "F 105 Determine measured

value" on the display or PC

The output signal jumps to the set error current

Supplementary electron-

ics - Second current

output

Supplementary elec-

tronics - Radio module

PLICSMOBILE

Advertising