11 Supplement

VEGAFLEX 86 • 4 … 20 mA/HART two-wire

42284-EN-130612

Ʋ Displayed value 1

Filling height Level

Ʋ Displayed value 2

Electronics temperature

Resolution, digital

< 1 mm (0.039 in)

Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

+860 … +1060 mbar/+86 … +106 kPa

(+12.5 … +15.4 psig)

Installation reference conditions

Ʋ Min. distance to installations

> 500 mm (19.69 in)

Ʋ Vessel

metallic, ø 1 m (3.281 ft), centric installation, process

fitting flush with the vessel ceiling

Ʋ Medium

Water/Oil (dielectric constant ~2.0)

4)

Ʋ Installation

Probe end does not touch the vessel bottom

Sensor parameter adjustment

No gating out of false signals carried out

Typical deviation - Interface measure-

ment

± 5 mm (0.197 in)

Typical deviation - Total level interface

measurement

See following diagrams

Typical deviation - Level measurement

5)6)

See following diagrams

Max. deviation - Version with reference

distance

± 10 mm (0.39 in)

Deviating upper dead band - Version with

reference distance

450 mm (17.7 in)

L

0

-2 mm (-0.079

")

2 mm (0.079

")

-10 mm (-0.394

")

5 mm (0.197

")

-5 mm (-0.197

")

0,15 m (5.906

"

)

0,03 m (1.18

"

)

0,1 m

(3.937

")

1

Fig. 42: Deviation VEGAFLEX 86 in coax version in water
1 Dead band - no measurement possible in this area

L Probe length

4)

With interface measurement = 2.0

5)

Depending on the installation conditions, there can be deviations which can be rectified with an adaptation of

the adjustment or a change of the measured value offset in the DTM service mode

6)

The dead bands can be optimizes by a false signal suppression.