4 mounting, 1 general instructions, 2 mounting instructions – VEGA VEGAFLEX 83 4 … 20 mA_HART two-wire Rod and cable probe - PFA insulated With SIL qualification User Manual

Page 16

Advertising
background image

16

4 Mounting

VEGAFLEX 83 • 4 … 20 mA/HART two-wire

44228-EN-130823

4 Mounting

4.1 General instructions

Protect your instrument further through the following measures

against moisture penetration:

Use the recommended cable (see chapter "Connecting to power

supply")

Tighten the cable gland

Loop the connection cable downward in front of the cable gland

This applies particularly to:

Outdoor mounting

Installations in areas where high humidity is expected (e.g. through

cleaning processes)

Installations on cooled or heated vessels

In the case of instrument housings with self-sealing NPT threads, it is

not possible to have the cable entries screwed in at the factory. The

openings for the cable glands are therefore covered with red protec-

tive caps as transport protection.
Prior to setup you have to replace these protective caps with ap-

proved cable glands or close the openings with suitable blind plugs.
The suitable cable glands and blind plugs come with the instrument.

Make sure that all parts of the instrument exposed to the process are

suitable for the existing process conditions.
These are mainly:

Active measuring component

Process fitting

Process seal

Process conditions are particularly:

Process pressure

Process temperature

Chemical properties of the medium

Abrasion and mechanical influences

You can find the specifications of the process conditions in chapter

"Technical data" as well as on the nameplate.

4.2 Mounting instructions

Mount VEGAFLEX 83 in such a way that the distance to vessel instal-

lations or to the vessel wall is at least 300 mm (12 in). In non-metallic

vessels, the distance to the vessel wall should be at least 500 mm

(19.7 in).
During operation, the probe must not touch any installations or the

vessel wall. If necessary, fasten the probe end.
In vessels with conical bottom it can be advantageous to mount the

sensor in the center of the vessel, as measurement is then possible

nearly down to the lowest point of the bottom. Keep in mind that

Protection against mois-

ture

Protective caps

Suitability for the process

conditions

Installation position

Advertising