10 Diagnostics and service

VEGAFLEX 83 • 4 … 20 mA/HART two-wire

44228-EN-130823

After an electronics exchange the settings of the electronics must

be checked and verified. Only then, the instrument is again ready for

operation.

10.6 Software update

The following components are required to update the sensor soft-

ware:

Sensor

Voltage supply

Interface adapter VEGACONNECT

PC with PACTware

Current sensor software as file

You can find the actual sensor software as well as detailed infor-

mation of the procedure under "www.vega.com/downloads" and

"Software".
You can find information about the installation in the download file.
Make sure that you are using the correct software with SIL qualifica-

tion.
Instruments with SIL qualification can only be updated with a respec-

tive software. An accidental update with a wrong software version is

impossible.

Caution:

Instruments with approvals can be bound to certain software ver-

sions. Therefore make sure that the approval remains effective with a

software update.
You can find detailed information on www.vega.com/downloads and

"Approvals".

10.7 How to proceed in case of repair

You can find a repair form as well as detailed information on how to

proceed under www.vega.com/downloads and "Forms and certifi-

cates".
By doing this you help us carry out the repair quickly and without hav-

ing to call back for needed information.
If a repair is necessary, please proceed as follows:

Print and fill out one form per instrument

Clean the instrument and pack it damage-proof

Attach the completed form and, if need be, also a safety data

sheet outside on the packaging

Please contact for the return shipment the agency serving you. You

can find the agency on our home page www.vega.com.