12 Supplement

VEGAFLEX 83 • 4 … 20 mA/HART two-wire

44228-EN-130823

Ʋ Installation

Probe end does not touch the vessel bottom

Sensor parameter adjustment

No gating out of false signals carried out

Typical deviation - Interface measure-

ment

± 5 mm (0.197 in)

Typical deviation - Total level interface

measurement

See following diagrams

Typical deviation - Level measurement

5)6)

See following diagrams

0,2 m

(7.874

"

)

0,1 m

(3.937

"

)

0,04 m

(1.575

")

1

L

0

-2 mm

(-0.079

")

2 mm

(0.079

")

15 mm

(0.591

"

)

-15 mm

(-0.591

")

Fig. 42: Deviation VEGAFLEX 83 in rod version (coated) in water
1 Dead band - no measurement possible in this area

L Probe length

Deviation - level measurement from 6 m

probe length

0.5 % of the probe length

5)

Depending on the installation conditions, there can be deviations which can be rectified with an adaptation of

the adjustment or a change of the measured value offset in the DTM service mode

6)

The dead bands can be optimizes by a false signal suppression.