6 Set up with the display and adjustment module

VEGABAR 82 • 4 … 20 mA/HART

45028-EN-131010

4. Position correction

In this menu item you compensate the influence of the installation

position of the instrument (offset) to the measured value.
5. zero adjustment

In this menu item you carry out the zero adjustment for the processs

pressure.
Enter the respective pressure value for 0 %.
6. span adjustment

In this menu item you carry out the span adjustment for the processs

pressure
Enter the respective pressure value for 100 %.

4. Position correction

In this menu item you compensate the influence of the installation

position of the instrument (offset) to the measured value.
5. Max. adjustment

In this menu item you carry out the max. adjustment for level
Enter the percentage value and the corresponding value for the max.

level.
6. Min. adjustment

In this menu item you carry out the min. adjustment for level
Enter the percentage value and the corresponding value for the min.

level.

The quick setup is hence finished.

6.4 Parameter adjustment - Extended adjustment

For technically demanding measurement loops you can carry out

extended settings in "Extended adjustment".

The main menu is divided into five sections with the following func-

tions:

Adjustment - Process

pressure measurement

Adjustment - Level meas-

urement

Main menu

Main menu