11 Supplement

VEGABAR 82 • 4 … 20 mA/HART

45028-EN-131010

Nominal range

Overload capacity, max.

pressure

Overload capacity, min. pres-

sure

0 … 5 psi

435 psi

0 psi

0 … 15 psi

510 psi

0 psi

0 … 30 psi

725 psi

0 psi

0 … 150 psi

1300 psi

0 psi

0 … 300 psi

1900 psi

0 psi

0 … 900 psi

2900 psi

0 psi

0 … +1450 psig
(only for measuring cell 17.5 mm)

2900 psig

0 psi

Output variable
For details on the operating voltage see chapter "Voltage supply"
Output signal

4 … 20 mA/HART

Range of the output signal

3.8 … 20.5 mA/HART (default setting)

Fulfilled HART specification

7.3

Signal resolution

0.3 µA

Failure signal current output (adjustable) ≥ 21 mA, ≤ 3.6 mA, last valid measured value
Max. output current

21.5 mA

Starting current

≤ 10 mA for 5 ms after switching on, ≤ 3.6 mA

Load

Load resistor, see chapter "Voltage supply"

Damping (63 % of the input variable),

adjustable

0 … 999 s

HART output values according to HART 7 (default setting)

2)

Ʋ First HART value (PV)

Linear percentage value

Ʋ Second HART value (SV)

Physical unit of the application

Ʋ Third HART value (TV)

Measuring cell temperature

Ʋ Fourth HART value (QV)

Electronics temperature

Output variable - Second current output
For details on the operating voltage see chapter "Voltage supply"
Output signal

4 … 20 mA (passive)

Range of the output signal

3.8 … 20.5 mA (default setting)

Signal resolution

0.3 µA

Failure signal current output (adjustable) Last valid measured value, ≥ 21 mA, ≤ 3.6 mA
Max. output current

21.5 mA

Starting current

≤ 10 mA for 5 ms after switching on, ≤ 3.6 mA

Load

Load resistor, see chapter "Voltage supply"

Damping (63 % of the input variable),

adjustable

0 … 999 s

2)

The output values can be assigned individually