VEGA VEGABAR 82 4 … 20 mA_HART - Operating Instructions User Manual

Page 70

Advertising
background image

70

11 Supplement

VEGABAR 82 • 4 … 20 mA/HART

45028-EN-131010

Deviation (according to IEC 60770)
Applies to the digital signal output (HART, Profibus PA, Foundation Fieldbus) as well as to the

analogue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal

measuring range/set span.
The specified values correspond to the value F

Kl

in chapter "Calculation of the total deviation".

Accuracy class

Non-linearity, hysteresis and re-

peatability with TD 1 : 1 up to 5 : 1

Non-linearity, hysteresis and re-

peatability with 5 : 1

0.05 %

< 0.05 %

< 0.01 % x TD

0.1 %

< 0.1 %

< 0.02 % x TD

0.2 %

< 0.2 %

< 0.04 % x TD

Influence of the product or ambient temperature
Thermal change zero signal and output span
Applies to the digital signal output (HART, Profibus PA, Foundation Fieldbus) as well as to the

analogue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal

measuring range/set span.
The thermal change of zero signal and output span corresponds to the value F

T

in chapter "Calcu-

lation of the total deviation (according to DIN 16086)".
Measuring cell - Standard

Medium or ambient tem-

perature T

Accuracy class 0.05 %,

0.1 %

Accuracy class 0.2 %

Accuracy class 0.2 %

with measuring range

0.1 bar

abs

-40 … 0 °C (-40 … +32 °F) < {0.15 % + 0.015 %/K x (-

T)} x {0.5+0.5 x TD}

< {0.1 % + 0.03 %/K x (-T)}

x {0.5+0.5 x TD}

< {0.30 % + 0.03 %/K x (-

T)} x {0.5+0.5 x TD}

0 … 40 °C

(+32 … +104 °F)

< {0.0075 %/K x (T -

20 °C)} x {0.5+0.5 x TD}

< {0.005 %/K x (T - 20 °C)}

x {0.5+0.5 x TD}

< {0.015 %/K x (T - 20 °C)}

x {0.5+0.5 x TD}

40 … 100 °C

(+104 … +212 °F)

< {0.15 % } x {0.5+0.5 x

TD}

< {0.005 %/K x (T - 20 °C)}

x {0.5+0.5 x TD}

< {0.3 % } x {0.5+0.5 x TD}

100 … 120 °C

(+212 … +248 °F)

< {0.15 % + 0.005 %/K x (T

- 100 °C)} x {0.5+0.5 x TD}

< {0.40 % + 0.01 %/K x (T -

100 °C)} x {0.5+0.5 x TD}

< {0.30 % + 0.01 %/K x (T -

100 °C)} x {0.5+0.5 x TD}

Measuring cell - climate-compensated
Compensated temperature range

0 … +100 °C (+32 … +212 °F)

Non-compensated temperature range

-40 … 0 °C (-40 … +32 °F), -100 … +130 °C

(+212 … +276 °F)