6 Set up with the display and adjustment module

VEGABAR 82 • Profibus PA

45031-EN-131107

The quick setup is hence finished.

6.4 Parameter adjustment - Extended adjustment

For technically demanding measurement loops you can carry out

extended settings in "Extended adjustment".

The main menu is divided into five sections with the following func-

tions:

Setup: Settings, for example, to measurement loop name, applica-

tion, units, position correction, adjustment, AI FB 1 Channel - scaling

- damping
Display: Settings, e.g., for language, measured value display, lighting
Diagnosis: Information, e.g. on instrument status, pointer, measure-

ment reliability, AI FB 1 simulation
Additional adjustments: PIN, date/time, reset, copy function
Info: Instrument name, hardware and software version, date of manu-

facture, sensor features
In the main menu point "Setup", the individual submenu points should

be selected subsequently and provided with the correct parameters

to ensure the optimum adjustment of the measurement. The menu

items are described in the following.

An address must be assigned to each Profibus PA instrument. Each

address may only be assigned once in the Profibus PA network. The

sensor is only recognized by the control system if the address is set

correctly.
When the instrument is shipped, address 126 is adjusted. This ad-

dress can be used for function test of the instrument and for con-

nection to a Profibus PA network. Then address must be changed to

integrate additional instruments.
The address setting is carried out either via:

The address selection switch in the electronics compartment of

the instrument (address setting via hardware)

The display and adjustment module (address setting via software)

PACTware/DTM (address setting via software)

Main menu

Setup - Instrument ad-

dress