6 Set up with the display and adjustment module

VEGABAR 82 • Profibus PA

45031-EN-131107

grammable linearization curve as well as the measured value memory

will be deleted.
Basic settings: Resetting the parameter settings incl. special

parameters to the default values of the respective instrument. A pro-

grammed linearization curve as well as the measured value memory

is deleted.
The following table shows the default values of the instrument. De-

pending on the instrument version or application, all menu items may

not be available or some may be differently assigned:

Reset - Setup

Menu item

Parameter

Default value

Sensor address

126

Measurement

loop name

Sensor

Application

Application pro-

cess pressure
Application level

No reset

Slave for elec-

tronic differential

pressure

No reset

Units

Unit of measure-

ment

mbar (with nominal measuring range

≤400 mbar)
bar (with nominal measuring rang-

es ≥1 bar)

Temperature unit °C

Position correc-

tion

0.00 bar

Adjustment

Zero/Min. adjust-

ment

0.00 bar
0.00 %

Span/Max. adjust-

ment

Nominal measuring range in bar
100.00 %

Damping

Integration time

0.0 s

Linearization

Linear

AI FB 1

Channel

Primary Value

Scaling format

Pressure

Scaling

0 % corresponds to 0 bar
100 % corresponds to measuring

range final value

Damping

PV FTime 0 s

Lock adjustment

Released