7 exchanging the electronics module – VEGA VEGABAR 82 Profibus PA - Operating Instructions User Manual

Page 58

Advertising
background image

58

9 Diagnosis, asset management and service

VEGABAR 82 • Profibus PA

45031-EN-131107

Caution:

The exchange may only be carried out in the complete absence of

line voltage.
In Ex applications, only a replacement part with appropriate Ex ap-

proval may be used.
Proceed as follows when carrying out the exchange:
1. Losen the fixing screw with the hexagon socket wrench
2. Carefully detach the cable assembly from the process assembly

1

2

5

3

4

Fig. 39: VEGABAR 82 in IP 68 version, 25 bar and lateral cable outlet, external

housing
1 Process assembly

2 Plug connector

3 Cable assembly

4 Connection cable

5 External housing

3. Loosen the plug connector
4. Mount the new process assembly on the measuring point
5. Plug the connector back in
6. Mount the cable assembly on the process assembly and turn it to

the desired position

7. Tighten the fixing screw with the hexagon socket wrench
The exchange is finished.
If there is no replacement part available on site, one can be ordered

from the agency serving you.
The necessary serial number can be found on the type label of the

instrument or on the delivery note.

9.7 Exchanging the electronics module

In case of a defect, the user can replace the electronics module with

another one of identical type.