6 Set up with the display and adjustment module

VEGABAR 82 • Profibus PA

45031-EN-131107

Caution:

Note the following, if the respective sensor is used as part of an over-

fill protection system according to WHG:
If a linearization curve is selected, the measuring signal is no longer

necessarily linear to the filling height. This must be considered by the

user especially when adjusting the switching point on the limit signal

transmitter.

Since the adjustment is very comprehensive, the menu points of

Function Blocks 1 (FB1) were put together in a submenu.

In menu item"Channel" you determine which measured value the

output refers to.

In menu item "Scaling format" you define the scaling variable and the

scaling unit for the level value on the display, e.g. volume in l.

In menu item "Scaling" you define the scaling format on the display

and the scaling of the measured level values for 0 % and 100 %.

Level measured value min.

Measured level value max.

Setup - AI FB1

Setup - AI FB1 - Channel

Setup - AI FB1 - Scaling

format

Setup - AI FB1 - Scaling