Quick start – VEGA VEGAFLEX 86 4 … 20 mA_HART - four-wire Coax probe User Manual

Page 2

Advertising
background image

2

Quick start

VEGAFLEX 86 • 4 … 20 mA/HART - four-wire

42285-EN-130314

Quick start

The quick start procedure enables a quick setup with many applica-

tions. You can find further information in the respective chapters of the

operating instructions manual.

Distance from the metallic vessel wall > 300 mm. Distance from

non-metallic vessel wall > 500 mm. The probe must not touch any

installations or the vessel wall.

For further information see chapter "Mounting".
1. Make sure that the power supply corresponds to the specifica-

tions on the type label.

2. Connect the instrument according to the following illustration

power supply

4...20mA

active

passive

common

IS GND

5

1

/L

/N

PE

2

+

( )

(-)

6

7

8

Fig. 1: Connection compartment with double chamber housing with mains

voltage

For further information see chapter "Connecting to power supply".

For standard applications we recommend selecting the "Quick setup"

in the display and adjustment module.

1. In this menu item you can select the application. You can choose

between level and interface measurement.

2. In the menu item "Medium - Dielectric constant" you can define

the medium type (medium).

3. Carry out the adjustment in the menu items "Min. adjustment" and

"Max. adjustment".

4. A "Linearization" is required for all vessels in which the vessel vol-

ume does not increase linearly with the level - e.g. in a horizontal

cylindrical or spherical tank. Activate the appropriate curve.

Mounting

Electrical connection

Set parameters