11 Supplement

VEGAFLEX 86 • 4 … 20 mA/HART - four-wire

42285-EN-130314

Typical deviation - Level measurement

4)5)

See following diagrams

Max. deviation - Version with reference

distance

± 10 mm (0.39 in)

Deviating upper dead band - Version with

reference distance

450 mm (17.7 in)

L

0

-2 mm (-0.079")

2 mm (0.079")

-10 mm (-0.394")

5 mm (0.197")

-5 mm (-0.197")

0,15 m (5.906")

0,03 m (1.18")

0,1 m

(3.937")

1

Fig. 32: Deviation VEGAFLEX 86 in coax version in water
1 Dead band - no measurement possible in this area

L Probe length

L

0

-2 mm (-0.079")

2 mm (0.079")

-10 mm (-0.394")

10 mm (0.394")

0,1 m (3.937")

0,05 m

(1.968")

0,1 m

(3.937")

0,25 m (9.842")

1

1

Fig. 33: Deviation VEGAFLEX 86 in coax version in oil
1 Dead band - no measurement possible in this area

L Probe length

Repeatability

≤ ±1 mm

Variables influencing measurement accuracy
Specifications for the digital measured value
Temperature drift - Digital output

±3 mm/10 K relating to the max. measuring range or

max. 10 mm (0.394 in)

Additional deviation through electromag-

netic interference acc. to EN 61326

< ±10 mm (< ±0.394 in)

4)

Depending on the installation conditions, there can be deviations which can be rectified with an adaptation of

the adjustment or a change of the measured value offset in the DTM service mode

5)

The dead bands can be optimizes by a false signal suppression.