11 Supplement
VEGAFLEX 86 • 4 … 20 mA/HART - four-wire
42285-EN-130314
Output variable
Output signals
4 … 20 mA/HART - active; 4 … 20 mA/HART - passive
Terminal voltage passive
9 … 30 V DC
Shortcircuit protection
Available
Potential separation
Available
Signal resolution
0.3 µA
Failure signal current output (adjustable) Last valid measured value, ≥ 21.0 mA, ≤ 3.6 mA
Max. output current
22 mA
Starting current
≤ 3.6 mA
Load (4 … 20 mA/HART - active)
< 500 Ω
Damping (63 % of the input variable)
0 … 999 s, adjustable
HART output values according to HART 7 (default setting)
1)
Ʋ First HART value (PV)
Linearised percentage value, level
Ʋ Second HART value (SV)
Distance to the level
Ʋ Third HART value (TV)
Measurement certainty, level
Ʋ Fourth HART value (QV)
Electronics temperature
Indication value - DIsplay and adjustment module
2)
Ʋ Displayed value 1
Filling height - Level
Ʋ Displayed value 2
Electronics temperature
Resolution, digital
< 1 mm (0.039 in)
Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1
Ʋ Temperature
+18 … +30 °C (+64 … +86 °F)
Ʋ Relative humidity
45 … 75 %
Ʋ Air pressure
+860 … +1060 mbar/+86 … +106 kPa
(+12.5 … +15.4 psig)
Installation reference conditions
Ʋ Min. distance to installations
> 500 mm (19.69 in)
Ʋ Vessel
metallic, ø 1 m (3.281 ft), centric installation, process
fitting flush with the vessel ceiling
Ʋ Medium
Water/Oil (dielectric constant ~2.0)
3)
Ʋ Installation
Probe end does not touch the vessel bottom
Sensor parameter adjustment
Gating out of false signals carried out
Typical deviation - Interface measure-
ment
± 5 mm (0.197 in)
Typical deviation - Total level interface
measurement
See following diagrams
1)
The output values can be assigned individually
2)
The indication values can be assigned individually
3)
with interface measurement = 2.0