VEGA VEGAFLEX 86 4 … 20 mA_HART - four-wire Coax probe User Manual

Page 70

Advertising
background image

70

11 Supplement

VEGAFLEX 86 • 4 … 20 mA/HART - four-wire

42285-EN-130314

1

2

0°C

(32°F)

-40°C

(-104°F)

55°C

(131°F)

80°C

(176°F)

200°C

(392°F)

150°C

(302°F)

3

4

-20°C

(-68°F)

Fig. 35: Ambient temperature - process temperature, version with temperature adapter
1 Ambient temperature

2 Process temperature (depending on the seal material)

3 Maximum permissible temperature - standard

4 Limited temperature range - plastic housing and stainless steel housing, electropolished

Vibration resistance

Ʋ Instrument housing

4 g at 5 … 200 Hz according to EN 60068-2-6 (vibration

with resonance)

Ʋ Rod probe

1 g with 5 … 200 Hz according EN 60068-2-6 (vibration

at resonance) with rod length 50 cm (19.69 in)

Shock resistance

Ʋ Instrument housing

100 g, 6 ms according to EN 60068-2-27 (mechanical

shock)

Ʋ Rod probe

25 g, 6 ms according to EN 60068-2-27 (mechanical

shock) with rod length 50 cm (19.69 in)

Electromechanical data - version IP 66/IP 67
Options of the cable entry

Ʋ Cable gland

M20 x 1.5

Ʋ Cable diameter (options)

5 … 9 mm (0.20 … 0.35 in)
6 … 12 mm (0.24 … 0.47 in)
10 … 14 mm (0.39 … 0.55 in)

Ʋ Cable entry

½ NPT

Ʋ Blind plug

M20 x 1.5; ½ NPT

Plug options

Ʋ Supply and signal circuit (only with low

voltage)

M12 x 1 plug

Ʋ Indication circuit

M12 x 1 plug

Wire cross-section (spring-loaded terminals)

Ʋ Massive wire, cord

0.2 … 2.5 mm² (AWG 24 … 14)

Ʋ Stranded wire with end sleeve

0.2 … 1.5 mm² (AWG 24 … 16)

Advertising