2) BASIC WIRINGS OF AN INTER-LOCK SYSTEM USING TWO SPLIT-DECODED KEYPADS

An inter-lock system needs two door controllers. This application example uses two keypad systems

with simple cross wire connection on their "Output 1 Inhibit" and "Inter-lock Control Output" terminals.

It is necessary to link up the "(-) GND" terminals of the two keypads as common ground to achieve

the inter-lock logical functions.

• Use keypad to open the door from outside

• Press egress button to open the door from inside

• Connect the door magnetic sensors on the doors to monitor their positions

• While door 1 is open, then, door 2 is forced to keep close, or vice versa

• Use N.O. Relay output for fail-secure lock; and N.C. output for fail-safe lock

• Please also see the "NOTE" stated in the Application Example (1)

- ALARM O/P
- KEY ACT O/P
- N.O.
- COM
- N.C.
- N.O.
- COM
- N.C.
- N.O.
- COM
- N.C.
- TAMPER
- GND(-)
- DOOR SENS
- O/P 1 INHIB
- INT. LOCK
- DU OUT
- DOOR BELL IN
- EG IN
- DATA I/O
- KEYPAD PWR
- GND(-)
- 12-24V DC

N.O.

ELECTRIC LOC

K

1N4004

DOOR 1

OUTPUT RELAY

1

N.O. Output for Fail-secure Loc

k

N.C. Output for Fail-safe Loc

k

N.C.

OUTPUT

1

OUTPUT 2

OUTPUT

3

DIGITAL KEYPAD

AD-1312 OR AP-960

EGRESS BUTTON

DOOR BELL BUTTON

N.O.

(-

)

(-

)

N.O.

DOOR

1

SENSING

COMMON GROUND

(-

)

DA-2800 OR DA-2801

DA-2800 OR DA-2801

CROSS WIRE CONNECTION FOR INTER-LOCK FUNCTIONS

- ALARM O/P
- KEY ACT O/P
- N.O.
- COM
- N.C.
- N.O.
- COM
- N.C.
- N.O.
- COM
- N.C.
- TAMPER
- GND(-)
- DOOR SENS
- O/P 1 INHIB
- INT. LOCK
- DU OUT
- DOOR BELL IN
- EG IN
- DATA I/O
- KEYPAD PWR
- GND(-)
- 12-24V DC

N.O.

ELECTRIC LOC

K

1N4004

DOOR

2

OUTPUT RELAY

1

N.O. Output for Fail-secure Loc

k

N.C. Output for Fail-safe Loc

k

N.C.

OUTPUT 1

OUTPUT

2

OUTPUT

3

DIGITAL KEYPAD

AD-1312 OR AP-960

EGRESS BUTTON

DOOR BELL BUTTON

N.O.

(-

)

(-

)

N.O.

DOOR

2

SENSING

Advertising