PowerWalker Battery Pack for VFI 10000R LCD User Manual

Page 14

Advertising
background image

13

EN

Indicates the ECO mode is enabled.

Indicates the Inversor circuit is working.

Indicates the output is working.

Battery information

Indicates the Battery capacity by 0-25%, 26-50%, 51-75%, and 76-100%.

Indicates the battery is

not connected.

Indicates low battery level and low battery voltage.

Input & Battery voltage information

Indicates the input voltage or frequency or battery voltage.
Vac: Input voltage, Vdc: battery voltage, Hz: input frequency

3-3. Audible Alarm

Description

Buzzer status

Muted

UPS status
Bypass mode

Beeping once every 2 minutes

Yes

Battery mode

Beeping once every 4 seconds

Fault mode

Beeping continuously

Warning
Overload

Beeping twice every second

No

Low battery

Beeping once every second

Battery unconnected
Over charge
EPO enable
Fan failure/Over temperature
Charger failure
IP fuse broken
Overload 3 times in 30min
EPO status
Cover of maintain switch is open
Fault
Bus start failure

Beeping continuously

Yes

Bus over
Bus under
Bus unbalance
Bus short circuited
Inversor soft start failure
High Inversor voltage
Low Inversor voltage
Inversor output short circuited
Negative power fault
Battery SCR short circuited
Inversor relay short circuited
Battery voltage loss
Parallel communication failure
Parallel output current unbalance
Over temperature
CPU communication failure
Overload