PowerWalker Battery Pack for VFI 10000R LCD User Manual

Page 20

Advertising
background image

19

EN

09

Battery backup time setting

Y

Y

Y

Y

Y

Y

10

Programmable output setting

Y

Y

Y

Y

Y

Y

11

Shutdown point for programmable output

Y

Y

Y

Y

Y

Y

12

Hot standby function enable/disable

Y

Y

Y

Y

Y

Y

13

Battery voltage adjustment

Y

Y

Y

Y

Y

Y

14

Charger voltage adjustment

Y

Y

Y

Y

Y

Y

15

Output voltage adjustment

Y

Y

Y

*Y means that this program can be set in this mode.
**Programmable output setting is not supported by 6000R(L)/10000R(L) models

Note: All parameter settings will be saved only when UPS shuts down normally with internal or external battery
connection. (Normal UPS shutdown means turning off input breaker in bypass mode).

01: Output voltage

Interface

Setting

Parameter 3: Output voltage
You may choose the following output voltage in parameter 3:
208: Presents output voltage is 208Vac
220: Presents output voltage is 220Vac
230: Presents output voltage is 230Vac
240: Presents output voltage is 240Vac

02: Output frequency

Interface

Setting

60 Hz, CVCF mode

50 Hz, Normal mode

ATO

Parameter 2: Output Frequency
Setting the output frequency. You may choose following three options
in parameter 2:
50.0Hz: The output frequency is setting for 50.0Hz.
60.0Hz: The output frequency is setting for 60.0Hz.
ATO: If selected, output frequency will be decided according to the
latest normal utility frequency. If it is from 46Hz to 54Hz, the output
frequency will be 50.0Hz. If it is from 56Hz to 64Hz, the output
frequency will be 60.0Hz. ATO is default setting.

Parameter 3: Frequency mode
Setting output frequency at CVCF mode or not CVCF mode. You may
choose following two options in parameter 3:
CF: Setting UPS to CVCF mode. If selected, the output frequency will be
fixed at 50Hz or 60Hz according to setting in parameter 2. The input
frequency could be from 46Hz to 64Hz.
NCF: Setting UPS to normal mode (not CVCF mode). If selected, the
output frequency will synchronize with the input frequency within
46~54 Hz at 50Hz or within 56~64 Hz at 60Hz according to setting in
parameter 2. If 50 Hz selected in parameter 2, UPS will transfer to
battery mode when input frequency is not within 46~54 Hz. If 60Hz
selected in parameter 2, UPS will transfer to battery mode when input
frequency is not within 56~64 Hz.
*If Parameter 2 is ATO, the Parameter 3 will show the current
frequency.

Note: If the UPS is set to CVCF mode, the bypass function will be disabled automatically.

But when a single UPS without parallel function is powered on with mains and before the UPS finished the

startup, there will be a few seconds of voltage pulse (same as the input voltage) on the bypass output.

If you need to remove the pulse on this mode to protect your load better, you could contact the dealer for help.

For the UPS with parallel function, this pulse situation won’t happen.