2-3. Single UPS Installation

Installation and wiring must be performed in accordance with the local electric laws/regulations and execute the
following instructions by professional personnel.

1)

Make sure the mains wire and breakers in the building are enough for the rated capacity of UPS to avoid the

hazards of electric shock or fire.

NOTE: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than the
UPS’s maximum input current. Otherwise the receptacle may be burned and destroyed.

2) Switch off the mains switch in the building before installation.

3) Turn off all the connected devices before connecting to the UPS and then switch off the internal output
breaker.

4) Prepare wires based on the following table:

Model

Wiring spec (AWG)

Input

Output

Battery

Ground

6000

10

10

10

6000L

10

10

10

10

10000

8

8

8

10000L

8

8

8

8

6000R

10

10

10

6000RL

10

10

10

10

10000R

8

8

8

10000RL

8

8

8

8

NOTE 1: The cable for 6000/6000L should be able to withstand over 40A current. It is recommended to use
10AWG or thicker wire for safety and efficiency.

NOTE 2: The cable for 10000/10000L should be able to withstand over 63A current. It is recommended to use
8AWG or thicker wire for safety and efficiency.

NOTE 3: The selections for color of wires should be followed by the local electrical laws and regulations.

5)

Remove the terminal block cover on the rear panel of UPS. Then connect the wires according to the following

terminal block diagrams: (Connect the earth wire first when making wire connection. Disconnect the earth wire last
when making wire disconnection!)

Terminal Block wiring diagram of 6000(L)/10000(L)

Input Neutral

Input Line

Output 2 Neutral

Output 2 Line

Output 1 Neutral

Output 1 Line