PowerWalker Battery Pack for VFI 10000R LCD User Manual

Page 22

Advertising
background image

21

EN

08: Bypass mode setting

Interface

Setting

Parameter 2:
OPN: Bypass allowed. When selected, UPS will run at Bypass mode
depending on bypass enabled/disabled setting.
FBD: Bypass not allowed. When selected, it’s not allowed for running in
Bypass mode under any situations.
Parameter 3:
ENA
: Bypass enabled. When selected, Bypass mode is activated.
DIS: Bypass disabled. When selected, automatic bypass is acceptable,
but manual bypass is not allowed. Manual bypass means users
manually operate UPS for Bypass mode. For example, pressing OFF
button in AC mode to turn into Bypass mode.

09: Battery backup time setting

Interface

Setting

Parameter 3:
000~999:
Set the maximum backup time from 0min to 999min. UPS
will shut down to protect battery after backup time arrives. The default
value is 990min.
DIS: Disable battery discharge protection and backup time will depend
on battery capacity.

10: Programmable output setting

Note:This function is not supported by 6000R(L)/10000R(L) model.

Interface

Setting

Parameter 3: Set programmable output. You may choose the following
three options:
ON: Programmable output is manually switched on timelessly.
OFF: Programmable output is manually switched off. However, if UPS
restarts, this setting will automatically go to “ATO” status.
ATO: Programmable output is automatically turned on or cut off
according to battery or load status. When the battery voltage is lower
than the setting point, or shutdown time arrives, the programmable
output will be cut off automatically. After the utility is recovering, the
output will turn on automatically. If overload happens, the
programmable output also will be cut off automatically. If it happens 3
times, the programmable output will be cut off until it is manually
switched on.

11: Shutdown point for programmable output

Interface

Setting

Parameter 2: 001.
Set shutdown time for programmable output.
Parameter 3: Shutdown time in minutes.
Setting range is from 0 to 300. When shutdown time arrives, the
programmable output terminal will be cut off. The default value is 30
minutes.

Advertising