Specifications – PowerWalker Battery Pack for VFI 10000R LCD User Manual

Page 30

Advertising
background image

29

EN

6. Specifications

MODEL

6000

6000R

10000

10000R

CAPACITY*

6000 VA / 4800 W

10000 VA / 8000 W

INPUT

Voltage
Range

Low Line Loss

110 VAC ± 3 % at 50% Load; 176 VAC ± 3 % at 100% Load

Low Line Comeback

Low Line Loss Voltage + 10V

High Line Loss

300 VAC ± 3 %

High Line Comeback

High Line Loss Voltage - 10V

Frequency Range

46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system

Phase

Single phase with ground

Power Factor

0.99 at 100% Load

OUTPUT
Output voltage

208/220/230/240VAC

AC Voltage Regulation

± 1%

Frequency Range
(Synchronized Range)

46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system

Frequency Range (Batt. Mode)

50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz

Overload

AC mode

100%~110%: 10min

110%~130%: 1min

>130% : 1sec

Battery mode

100%~110%: 30sec
110%~130%: 10sec

>130% : 1sec

Current Crest Ratio

3:1 max

Harmonic Distortion

≦ 3 % @ 100% Linear Load; ≦ 6 % @ 100% Non-linear Load

Transfer
Time

Line

Battery

0 ms

Inversor

Bypass

0 ms

Inversor

ECO

<10 ms

EFFICIENCY
AC mode

> 89%

Battery Mode

> 88%

BATTERY

Standard
Model

Type & Numbers

12 V / 7 Ah x 20

12 V / 9 Ah x 20

Recharge Time

7 hours recover to

90% capacity

3 hours recover to

90% capacity

9 hours recover to 90%

capacity

4 hours recover to 90%

capacity

Charging Current

1 A ± 10% (max.)

2 A ± 10% (max.)

1 A ± 10% (max.)

2 A ± 10% (max.)

Charging Voltage

14.4 V ± 1%

Long-run
Model

Type

Depending on applications

Numbers

18 - 20

Charging Current

4 A ± 10% (max.)

2 A ± 10% (max.)

4 A ± 10% (max.)

2 A ± 10% (max.)

Charging Voltage

14.4 V ± 1%

PHYSICAL

Standard
Model

Dimension, D X W X H

592X250X576

UPS unit:

580X438X133

Battery pack: 580X438

X133

592 X250 X576

UPS unit:

668X438X133

Battery pack: 580X438

X133

Net Weight (kgs)

81

UPS unit: 17

Battery pack: 57

83

UPS unit: 20

Battery pack: 63

Long-run
Model

Dimension, D X W X H

592 X250 X576

580 X 438 X 133

592 X250 X576

668 X 438 X 133

Net Weight (kgs)

25

17

27

20

ENVIRONMENT
Operation Temperature

0 ~ 40°C (the battery life will down when > 25°C)

Operation Humidity

<95 % and non-condensing

Operation Altitude**

<1000m

Acoustic Noise Level

Less than 55dB @ 1 Meter

Less than 58dB @ 1 Meter

MANAGEMENT
Smart RS-232 or USB

Supports Windows®2000/2003/XP/Vista/2008/7, Linux, Unix and MAC

Optional SNMP

Power management from SNMP manager and web browser

* Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC.
**If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
***Product specifications are subject to change without further notice.

Advertising