THE PRODUCT IN OPERATION

2.2.4.6. Wiring plans for downlights with
POWERTRONIC

®

ECG with cable clamp

The wiring of independent devices has particular require-
ments, particularly from the point of view of the EMC.
For this reason the following section is dedi cated to
dealing with such applications.

Notes:
• Use short lamp cabling: approx. 0.5 m
• The PE-LUM connection may only be used for earthing

the luminaire.

15

Where longer cables (<1.5 m) are necessary, the PE should
be connected to the ECG and from the ECG to the lumi-
naire; the lamp cables must be twisted; ferrites must be
installed on the lamp cables.

Example of looping in a ferrite in order to reduce EMC
emissions

Figure 13: Wiring plan PTi 35 to 70 I with mains looping

Figure 16: (Sample) Wiring plan for improved EMC behavior

Figure 17: Looping in ferrite cores to reduce EMC emissions

Figure 14: Wiring plan PTi 20 I with mains looping

Figure 15: PTi 100 and 150 I as well as PT-FIT 35 to 70 I wiring plan

Ferrite core (1 twist)