THE SYSTEM HID LAMP AND ECG

7

1.2.5. Application areas
1.2.5.1. Indoor, outdoor
POWERTRONIC

®

PTi and PT-FIT ECGs have been devel-

oped for indoor applications and for these they are suitable.

Any guarantee claims against OSRAM POWERTRONIC

®

PTi and PT-FIT ECGs are void if they are used in outdoor
areas – no matter what the IP classifi cation of the installed
luminaires may be.

PTi and PT-FIT devices conform to the requirements of
IEC/EN 61547: Resistance to interference under surge
voltage between L and N 1 kV, between L/N and PE 2 kV
for devices with input power > 25 W, with these values
divided by two where power is < 25 W. These levels of
test precision (test levels) comply with installation classes
2 (< 25 W) and 3 (> 25 W) in accordance with
IEC/EN 61000-4-5 Annex A.

Comparison of CCG and POWERTRONIC

®

Magnetic control gear (CCG)

POWERTRONIC

®

electronic control gear

Energy consumption

100

For indoor applications: 10 to 15 % savings over
the whole service life

For outdoor applications: up to 30 % savings over
the whole service life through dimming function (3DIM)

Lamp life

100

Up to 30 % depending on lamp type and
application

Lamp warm-up

Depends on lamp type: generally approx. 60–90 sec,
up to 90 % of nominal luminous fl ux

Up to 50 % faster

Color stability (HCI/HQI)

Color variation possible

Substantially improved color stability; both initially and over the
whole service life

Shutdown at end of
lamp life

None or only primitive shutdown mechanisms

Continuous parameter control, intelligent shutdown mechanisms

Shutdown of ignition

Only with timer-based ignition devices

Default shutdown of ignition after 20 minutes

Light fl icker

Visible fl icker

Flicker-free thanks to operation at 100–240 Hz

Power constancy

Increased wattage over the whole service life, wattage also
depends on temperature and mains voltage fl uctuations
and cable length

± 3 % over the whole service life, independent of temperature,
mains voltage fl uctuations and cable length

Usability

3 components, complex wiring

1 device, simple wiring

Size and weight

Heavy, more components, can be quite large

Lightweight and compact

Power factor correction (PFC)

0.5–0.95, substantial fl uctuations due to age

≥ 0.95

Noise generation

Possible detectable humming

Almost soundless

Bi-directional data exchange

Not possible

Generally possible (DALI

®

)

Dimming

Possible to a limited extent (additional components necessary)

3 different dimming modes possible for outdoor ECG
(DALI

®

, StepDIM and AstroDIM)

Lightning protection

Not necessary

For outdoor ECG up to 10 kV

The above values and statements are based on research and experience with OSRAM POWERTRONIC

®

devices and are therefore not

trans ferable on a one-to-one basis to the devices made by other manufacturers.

POWERTRONIC

®

PTo ECGs were developed for deploy-

ment in outdoor areas. Due to their robustness, they offer
substantial improvements in the way they deal with out-
door weather conditions (e.g. moisture or temperature
changes), vibrations or also transient power supply con-
ditions (caused by switching or lightning (EN 61000-4-5
Section 1). Besides street lighting, PTo ECGs can be used
in industrial applications. Both areas of application make
tough demands for surge voltage stability. PTos exceed
the standards required for Installation Class 4, with test
levels for L to N of 3 kV and for L/N to PE of 4 kV.