Hid lamp, Pto ecg, The product in operation – OSRAM POWERTRONIC PT-FIT I ECG for HID lamps, with cable clamp User Manual

Page 16

Advertising
background image

THE PRODUCT IN OPERATION

2.2.4.7. Wiring plans for POWERTRONIC

®

ECG PTo

The PTo devices

1

provide 3 different dimming modes;

these are provided under the 3DIM feature.

16

2.2.4.8. Stripping length
The required stripping length of wiring depends on the ter-
minal type used by the ECG. A length of 8.5 to 9 mm or 10
to 11 mm is appropriate, depending on the terminal ver-
sion. The exact stripping length is given on each ECG.

2.2.5. Inrush current limiter
Due to the initial charging of the storage capacitor respon-
sible for internal power supply, a strong pulse of inrush
current occurs on switching on an ECG. This pulse lasts
for a very short time (< 1 ms). For this reason, if very many
ECGs are switched on at the same time (especially when
switching on at a peak in mains voltage) a substantially
stronger overall current fl ows for a short time. Therefore
appropriate switching and protective devices are neces-
sary to ensure suffi cient current. The maximum number of
ECGs allowed per circuit breaker can therefore be calcu-
lated by observing the total maximum inrush current im-
pulse per device and its duration. This value is to be found
in the datasheet for each individual POWERTRONIC

®

ECG.

Further information:

www.osram.com/powertronic

The ECG must be appropriately wired depending on the
dimming mode:

1

With the exception of the PTo 35

Figure 18: 3DIM – wiring in DALI

®

mode

Figure 19: 3DIM – wiring in StepDIM mode

Figure 20: 3DIM – wiring in AstroDIM mode

Further information on the 3DIM functionality can be found
in the 3DIM application guide.

POWERTRONIC

®

3DIM ECG

HID lamp

HID out

Lamp

Mains cable
50/60 Hz

L

LH

LL

N

SD

DA

DA

PTo ECG

POWERTRONIC

®

3DIM ECG

HID lamp

HID out

Lamp

Mains cable
50/60 Hz

DALI

®

bus/

DALI

®

controller

L

LH

LL

N

SD

DA

DA

PTo ECG

POWERTRONIC

®

3DIM ECG

HID lamp

HID out

SD control
switch

Mains cable
50/60 Hz

L

N

SD

DA

DA

PTo ECG

Lamp

LH

LL

Advertising