2.4.6 Supply Voltage for QT

with 30 mm height

Valid for: QT-FH MULTIWATT and QT-FQ
Recommended voltage range for continuous operation
AC
voltage

198V ... 264V, 50/60 Hz

DC voltage

176V ... 264V

Performance at undervoltage

Lamp ignition

U

N

≥ 198V Î reliable lamp start

Voltage drop during operation

U

N

≥ 176V Î operation possible

U

N

< 176V Î damage to ECG

possible


2.4.7 ECG for 120V / 277V

Line Voltage

T5/

∅ 16 mm fluorescent lamps are also getting more popular in North

America (USA, Canada). Historically in the US-market have been
established lamps in 4 ft length besides the types of 240 cm. 4 ft is also
known as 48 inch type (1 ft = 30.48 cm) and is acc. to our typical 120 cm
types. Related to the straight fluorescent types FH

®

…HE and FQ

®

…HO

this means 1,149 mm for FH

®

28 W HE and FQ

®

54 W HO.


OSRAM SYLVANIA offers the complete range for FH

®

…HE and FQ

®

…HO

under PENTRON ECG. The specification there is PENTRON High
Performance T5 lamps for FH

®

and PENTRON High Output T5 for FQ

®

lamps.

OSRAM SYLVANIA also offers the ECG for the North American line
voltages 120 V / 277 V und 60 Hz line frequency as shown at a glance:

MULTIWATT ECG for FH

®

fluorescent lamps: 14, 21, 28 and 35 W HE

Types:

QTP 1x28T5/UNV PSN

suitable for 120-277 V

QTP 2x28T5/UNV PSN

suitable for 120-277 V


ECG to operate FQ

®

54 W HO

Types:

QTP 1x54T5UNV/PSN

suitable for 120-277 V

QTP 2x54T5UNV/PSN

suitable for 120-277 V


For a large number of differnt lamp types including T8 OCTRON a variety
of dimmable and non dimmable types is available.

Information about availability under:

OSRAM LIGHT CONSULTING (OLC)
Hellabrunner Straße 1
81536 München

Tel:

+49-89-6213 3076

Fax: +49-89-6213 2020

2.5 Automatic

Lamp

Restart

With all QUICKTRONIC

®

for operation of T5/

16 mm-fluorescent

lamps FH

®

…HE, FQ

®

…HO and FC

®

, automatic restart takes place after

a change of lamp provided the power supply is maintained.


Should in the case of a twin-lamp ECG no automatic lamp restart take
place after lamp replacement and could an ECG-failure be excluded,
please proceed as follows: