7.1.5 QT-FQ…F/CW

-21 mm height-

ECG-type Seque

nce

PIN

1

PIN

2

PIN

3

PIN

4

PIN

5

PIN

6

PIN

7

QT-FQ 1x24-39 F/CW

1-7

2 2 1 1

QT-FQ 1x54 F/CW

1-7

2 2 1 1

QT-FQ 1x80 F/CW

1-7

2 2 1 1

QT-FQ 2x24-39 F/CW

1-7

1 1 2 2 2 2

QT-FQ 2x54 F/CW

1-7

1 1 2 2 2 2

QT-FQ 2x80

1-7

1 1 2 2 2 2

7.1.6 QT-FC

ECG-type Seque

nce

PIN

1

PIN

2

PIN

3

PIN

4

PIN

5

PIN

6

PIN

7

QT-FC 1x55/230-240 S

1-4

2 2 1 1

7.2 Terminal

Types

WAGO 250

WAGO 251

WAGO 251-

mini

QT-FH MULTI CW

X

QT-FQ … CW

X

QT-FH 1x14, 21

X

QT-FH 3, 4x14

X

QT-FH...F/CW

X

QT-FQ...F/CW

X

QTi

X


Special features of particular terminals: see Section 3.1ff

7.3 Inrush

Currents

QUICKTRONIC

®

INTELLIGENT

Max. number of ECGs

with automatic circuit

breakers

Ip[A]

T

H

[µs] 10A

16A

QTi 1x14/24/21/39

1 155 26

41

QTi 1x28/54

1 155 26

41

QTi 1x35/49/80

1 155 26

41

QTi 2x14/24/21/39

1 200 19

31

QTi 2x28/54

1 200 19

31

QTi 2x35/49

1 200 19

31

QT-FQ 2x80

60 230 5

9


QUICKTRONIC

®

21 mm height

Max. number of ECGs

with automatic circuit

breakers

Ip[A]

T

H

[µs] 10A

16A

QT-FH 1x14-35 F/CW

17 155 25

41

QT-FH 2x14-28 F/CW

20 210 17

28

QT-FQ 1x24-39 F/CW

17 155 25

41

QT-FQ 1x54 F/CW

27 170 17

28

QT-FQ 1x80 F/CW

27 170 17

28

QT-FQ 2x24-39 F/CW

27 170 17

28

QT-FQ 2x54 F/CW

32 210 10

17

QT-FQ 2x80 F/CW

39 260 8

14