He and fq, Ho, and 25 °c for fc, Luminous flux fh – OSRAM QUICKTRONIC-M ECG for circular FL 16 mm User Manual

Page 44

Advertising
background image

43


If, however, the temperature at the tc point is permanently 10 °C or more
below the maximum, the expected service life of the unit will be
approximately doubled.


3.9.2.2 Ambient Temperature

ECG : ta

According to EN 60598-1, ta (a stands for ambient) is the maximum value
of the steady state temperature at which, during normal operation, limit
temperature tc is not exceeded at the measuring point.

Also according to EN 60598-1, there are precisely defined testing and
measuring requirements for both surface mounted luminaires (pendant and
portable, for example floor lights) and recessed luminaries.

3.9.3 Lamp

Temperature

The maximum values specified in the lamp documentation for cold-spot
temperature (see Technical Specification T5 Fluorescent Lamps) are
important operating criteria for the lamp and must not be exceeded nor
fallen below under any circumstances in order to achieve optimum
luminous flux. The ambient temperature to reach the maximum lumen
output is 35°C for T5/

∅ 16 mm fluorescent lamps FH

®

..HE and FQ

®

...HO,

and 25 °C for FC

®

- circular fluorescent lamps


Further lamp and ECG should not heat each other. ECG should be
dissipated through good thermal connection between ECG and luminaire
housing.

3.9.3.1 Maximum Luminous

Flux for T5/

16 mm-

Fluorescent Lamps

Usually, T5-fluorescent lamps reach their standard electric properties (rated
values) which are used for lighting design purposes at ambient
temperatures of 25 °C. Their maximum light outputs, however, are
achieved at ambient temperatures of 35 °C.

Luminous flux FH

®

…HE and FQ

®

…HO fluorescent lamps related to the lamp ambient

temperature

Placement of th filaments for T8 lamps

Placement of the filaments for T5 lamps

Cold Spot

T5 FH28W (nearly constant power supply): Luminous flux / Voltage - Horseshoe

0%

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

55%

60%

65%

70%

75%

80%

85%

90%

95%

100%

relative lamp voltage

re

lat

ive light

out

put

COLD SPOT temperature

50°C

45°C

40°C

35°C

30°C

25°C

15°C

90°C

85°C

80°C

75°C

70°C

65°C

60°C

55°C

5°C

10°C

0°C

20°C

ambient temperature

-5°C

75°C

25°C

35°C

45°C

5°C

-25°C

55°C

T5 FQ54W (nearly constant power supply): Luminous flux / Voltage - Horseshoe

0%

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

60%

65%

70%

75%

80%

85%

90%

95%

100%

relative lamp voltage

re

lative light output

COLD SPOT temperature

-5°C

50°C

45°C

40°C

35°C

30°C

25°C

15°C

90°C

85°C

80°C

75°C

70°C

65°C

60°C

55°C

5°C

10°C

0°C

20°C

ambient temperature

-5°C

78°C

25°C

35°C

45°C

5°C

-25°C

55°C

Advertising