OSRAM QUICKTRONIC-M ECG for circular FL 16 mm User Manual

Page 48

Advertising
background image

47

1. The test adapter is inserted behind the release lever of the 45°-

plug-in terminals or, in the case of combi-wiring terminals, in the
respective non-wired IDC or horizontal plug-in contact.

2. Instead of the lamps the two dummy lamps are inserted in the

lampholders of the empty luminaire.

3. Measure the resistance between A and B and between C and D.

The resistance between A and B and between C and D should be
100 Ω.

4. Measure the resistance between E and F and between G and H in

the same way.


If the measured resistance is not 100

Ω, the wiring is incorrect.





Dummy 1

Dummy 2

Adapter

A
B

C
D

E
F

G
H