EntelliGuard™ 800–2000 A Power Circuit Breakers
Chapter 6. Contact Maintenance

24

Contact Replacement on EGX08, EGS16,

EGF16, EGH16, EGS20, and EGF20 Breakers

For the following procedures, illustrated in Figure 20, the

breaker must be removed from its compartment and

placed on a suitable working surface. Remove the arc

chutes and interphase barriers, as described in Section

6.2.

Stationary Contacts

Use the following procedure to replace the stationary con-

tacts.

1. Remove the four screws holding the arc runner in

place and remove the arc runner. Take care not to

damage or lose the insulating washer underneath

the lock washer and flat washer on the two lower

screws.

2. For replacement of stationary main and intermedi-

ate contacts:

a. Release each contact spring by holding the corre-

sponding intermediate or main contact, extend-

ing the spring, and removing the spring from the

contact. The end pieces of each spring have a

small hole for inserting a spring puller.

b. Remove each contact as its spring is disengaged.

Clean off the existing lubricant on the pivot area.

Replace with a small amount of GE Lubricant

D6A15A1 (MobilGrease 28, catalog number

193A1751P1).

c. Insert each replacement main and intermediate

contact and secure with its contact spring. Note

that main and intermediate contacts are

differentiated by the number of chamfers on the

corners of the contact surfaces, as illustrated in

Figure 21. It is important that this distinction be

observed when replacing the contacts.

3. For replacement of stationary arcing contacts, as

illustrated in Figure 22:

a. Remove the two screws and lock washers securing

the arcing contact pivot to the assembly and

remove the pivot.

b. Remove the insulating spacers, contact pin, and

arcing contacts.

c. Insert the replacement arcing contacts, the con-

tact pin, and insulating spacers.

d. Place the arcing contact pivot in position and

secure with its two screws and lock washers.

4. Place the arc runner in position and secure with its

four screws. Ensure that the insulating washers are

in place on the lower screws. Tighten the screws to

45 in-lb.

Movable Contacts

Use the following procedure to replace the movable con-

tacts.

1. Remove the snap ring from the coupling pin and

slide out the pin.

2. Remove the screw, washer, and spring from one side

of the pivot pin. Carefully remove the pivot pin.

3. Slip out the contact arms.
4. Clean any existing lubricant from the pivot pin.

Place a small amount of GE Lubricant D6A15A1

(MobilGrease 28, catalog number 193A1751P1) on

the pivot pin and the pivot surfaces of the new

contact arms.

5. Install the new arm, insert the pivot pin, and replace

the pivot spring, washer, and screw. Tighten to 90

in-lb.

6. Install the coupling pin and secure with the snap

ring.

7. Adjust the contacts as described in Section 6.5.