EntelliGuard™ 800–2000 A Power Circuit Breakers
Chapter 8. Accessory Maintenance

48

8.7 Network Interlock

The Network Interlock provides a means of locking out a

breaker to coordinate its operation with other breakers in

the distribution network. When activated by the

EntelliGuard Messenger, the Network Interlock prevents

the breaker from closing. When the EntelliGuard

Messenger issues a RESET signal, the breaker can be

closed either remotely or locally. The Network Interlock

accessory includes a manual reset lever to reset the device

in the absence of a signal from the EntelliGuard

Messenger.
The Network Interlock consists of a trip coil, a reset coil,

and a status switch. The device connections to the

secondary disconnect are shown in Figure 62. When

voltage is applied across the trip coil, the device locks out

the breaker. Conversely, when voltage is applied to the

reset coil or when the reset lever is depressed, the Network

Interlock resets, allowing the breaker to close. The

Network Interlock does not close the breaker itself.
Renewal parts for the Network Interlock are available as a

complete kit or as a module only. The Network Interlock

accessory is only available on electrically operated

breakers.






Figure 62. Network Interlock connections to the secondary disconnect.

Removing the Network Interlock Module

Use the following procedure to remove the Network

Interlock.

1. Disconnect the six wires from the Network Interlock

device. Label each wire as it is removed. Cut wire ties

as necessary.

2. Remove the manual reset assembly by removing the

two hex-head screws as shown in Figure 65.

3. Remove the accessory mounting plate as shown in

Figure 63.

4. Remove the Network Interlock module from the

mounting plate by removing the three sets of nuts

and washers, as shown in Figure 64.

Installing the Network Interlock Module


Use the following procedure to install the Network
Interlock module as a replacement.
1. Open the circuit breaker and remove it from the

cubicle or substructure. Check to ensure the breaker

closing springs are DISCHARGED.

2. Carefully place the circuit breaker on a suitable

working surface, resting on the primary disconnects,

so that the bottom of the circuit breaker is accessible.

3. Fasten the Network Interlock module to the accessory

mounting plate using three sets of # 8-32 nuts, spring

washers, and flat washers as shown in Figure 64.

4. Fasten the Shunt Trip accessory to the mounting plate

beside the Network Interlock. See Section 8.2 or DEH-

168 for detailed instructions.

5. Assemble the accessory mounting plate to the circuit

breaker frame using four sets of # 10-32 screws, spring

washers, and flat washers as shown in Figure 63

6. Ensure the Network Interlock is in the RESET state

(shown in Figure 66) by manually rotating the reset

lever counterclockwise. If the Network Interlock was

SET, this operation will cause the set lever to retract

(counterclockwise) away from the trip paddle.

7. With the breaker open, charge the breaker closing

springs. Do not close the breaker. Adjust the gap

between the Network Interlock set lever and trip

paddle by rotating the socket-head adjusting screw as

shown in Figure 66. The distance between the set lever

and the trip paddle must be between 0.060 and 0.090

inch.

8. Connect the six wires to their corresponding terminals

on the Network Interlock device.

9. Reset the Network Interlock by pushing the manual

reset button. The Network Interlock status circuit

should be open. Close the breaker manually or

electrically. The breaker should close properly.

10. Set the Network Interlock by applying 120 VAC across

terminals 15 and 21 on the secondary disconnect. The

breaker should trip open and the status circuit should

change from open to close.

11. Charge the breaker manually or electrically. Close the

breaker. The breaker should trip open, discharging

the closing springs.

12. Reset the Network Interlock by applying 120 VAC

across terminals 20 and 21 on the secondary

disconnect. The status circuit should change from

closed to open.

13. Charge and close the breaker. The breaker should

close properly.

14. Set the Network Interlock, and repeat Steps 9 through

13.


15

NI Set

Coil

20

21

NI Reset

Coil

1

3

2

16

19

4

5

NI Status

Contact