EntelliGuard™ 800–2000 A Power Circuit Breakers
Chapter 7. Maintenance of Standard Parts and Assemblies

32

7.3 Flux Shifter

The function of the flux shifter, illustrated in Figure 33, is

to actuate the trip shaft and trip the breaker upon receiv-

ing a signal from the EntelliGuard Messenger™.

Flux Shifter Adjustment

The only adjustment required to the flux shifter mecha-

nism is the trip rod length. As shown in Figure 34, the

clearance between the trip rod end and the trip paddle is

set to 0.11 ± 0.03 inch. To make this adjustment, open the

breaker and charge the closing springs to restore the

mechanism to the Reset position. Loosen the lock nut on

the trip rod, rotate the adjuster until the proper gap is

attained, then retighten the lock nut.

Removing the Flux Shifter

The following procedure is illustrated in Figure 35.

1. Remove the snap ring connecting the reset arm to

the main shaft and slide the arm off its mounting

point.

2. Unplug the connector at the end of the flux shifter

leads.

3. Remove the two mounting bolts and lock washers

from underneath the breaker base, then lift off the

flux shifter.

Installing the Flux Shifter

The following procedure is illustrated in Figure 35.

1. Put the replacement flux shifter into position, lining

up the solenoid plunger with the end of the trip rod

and the operations counter link (if present) with

the end of the reset arm. Insert the two bolts and

lock washers from beneath the bottom plate of the

breaker and tighten to 32 in-lb.

2. Slide the end of the reset arm onto the connection

on the breaker main shaft and secure with the snap

ring.

3. Connect the leads to the secondary disconnect.

Figure 33. Flux shifter.

Figure 34. Flux shifter adjustment.