5 adjusting the contacts – GE Industrial Solutions EntelliGuard 800–2000 A Frames, 240–600 Vac Maintenance Manual User Manual

Page 36

Advertising
background image

EntelliGuard™ 800–2000 A Power Circuit Breakers
Chapter 6. Contact Maintenance

26

6.5 Adjusting the Contacts

Adjust the contact depression whenever contacts are

replaced. In addition, check and adjust, as necessary, at

the normal maintenance interval.

Contact Adjustment on EGS08, EGF08, and

EGH08 Breakers

The following procedure is illustrated in Figure 23.

1. Contact depression is correct if the center of the roll

pin falls within the two sides of the scribed adjust-

ment mark on the side of the stationary main con-

tact.

2. If adjustment is necessary, remove the nut, washer,

and bushing from the end of the pivot bolt securing

the insulator link assembly to the movable contact

arm, then remove the bolt and other washer and

bushing.

3. Turn the contact adjusting link in or out of the insu-

lator link assembly. Increase its length to increase

contact depression and shorten the link to decrease

contact depression.

4. Reassemble the insulator link assembly to the con-

tact arm with the pivot bolt, nut, two washers, and

two bushings.

Contact Adjustment on EGX08, EGS16,

EGF16, EGH16, EGS20, and EGF20 Breakers

The following procedure is illustrated in Figure 24.

1. Remove the arc chutes and phase barriers, as

described in Section 6.2.

2. To establish a reference for measurement, fasten

the aluminum arc chute retainer to the breaker

mechanism frame with small C clamps, as shown.

Ensure that the C clamps do not interfere with any

moving parts.

3. Measure dimension ‘A’ with the contacts open and

again with the contacts closed. Note that the meas-

urement is made from the second contact spring

end (first stationary main contact). The difference

in the measurements should be 0.06–0.10 inch,

which provides 0.05–0.08 inch main contact depres-

sion.

4. To adjust contact depression, do the following:

a. Remove the retaining ring from one side of the

pin connecting the drive link to the movable con-

tact arms and remove the pin.

b. Adjust the depression by turning the link in one-

half-turn increments. Note that the link has left-

hand threads. One-half turn changes dimension

A by about 0.03 inch, which is equivalent to about

0.02 inch in contact depression.

5. Repeat for all poles.

Figure 23. Contact adjustment on EGS08, EGF08, and EGH08 breakers.