GE Industrial Solutions Power Break II Replacment Stop Block Kit User Manual

Power break, Installation

Advertising
background image

DEH40466 Installation Instructions

R04

g

Power

Break

®

II Circuit Breakers

Replacement Stop Block Kit

Application

This kit is provided to replace the stop block assembly in the

Power Break II insulated-case circuit breakers. The parts

included in this kit are illustrated in Figure 1 and listed in Table

1. In the following instructions and figures, numbers in

brackets refer to the items in Table 1.


Figure 1:Parts included in the stop block gasket kit

Item Part

# Description

Qty.

1

N170P19024 SPRING ASSEMBLY SCREW

1

2 192A6368P1

SPACER

1

3

10054595G1 ASSEMBLY, STOP BLOCK

1

4

192A6976P233 BOLT, N22P21008B6 W/NYLON

PATCH

4

5

N405P41B6

LOCKWASHER, STL SPRING 1/4

4

6

10103378P1 5/32 ALLEN WRENCH TOOL

1

Table 1. Parts list for the stop block gasket kit.

Installation

WARNING: Before beginning this procedure, turn

the breaker

OFF

, disconnect it from all voltage

sources, and discharge the closing springs.

AVERTISSEMENT: Mettre le disjoncteur à

OFF

, le

débrancher de toutes les sources de tension et

déclencher les ressorts de fermeture avant

d'entamer cette procédure.

[1]

[2]

1. Turn the breaker off and discharge the closing spring by

depressing the

OFF

and

ON

buttons in the sequence

OFF-

ON-OFF

. Verify that the breaker

OFF-ON

indicator shows

OFF

on a green background and that the charge

indicator shows

DISCHARGED

on a white background.

[4]

[5]

2. A draw-out and stationary-mounted breaker need not

be removed from their enclosures, but be careful that all

primary and control power to the breakers are

disconnected.

[3]

3. Loosen the four #8-32 screws that attach the trim plate

to the breaker, if present, and remove the trim plate.

4. Loosen the four screws at the corners of the breaker

cover. Operate the charging handle one time and hold it

extended to remove the cover from the breaker face, as

illustrated in Figure 2.

[6]

Figure 2: Removing or installing the breaker top cover.

Advertising