Operating Manual VH Series 700 - 1000 -1500 – 2000 VA UL

7

TROUBLESHOOTING

Whenever a malfunction occurs, first check external factors (e.g. connections, temperature, humidity or load) to determine
whether the problem is caused by the unit itself or by its environment. Subsequently check the thermal circuit breaker: it
may be tripped. If so: reset it (see fig. 3.4a/b) and be sure that the UPS is not overloaded.
The following chart is a simple troubleshooting checklist only. If the suggested solution does not succeed, or if the
information is insufficient to solve the problem, please contact your dealer or consult www.gedigitalenergy.com.

PROBLEM

POSSIBLE CAUSE

SOLUTION

Thermal Circuit Breaker (TCB) tripped

UPS overload

Reduce load, reset TCB (2, fig. 3.4a/b)

System failure

Contact your dealer or consult
www.gedigitalenergy.com

UPS will not switch on (without using
'battery start') and the output has
been off for a few secs. (see also
4.3.4)

Line cord not connected

Read 3.5.2 Connect line cord

Dead wall socket outlet, or mains
voltage out of limits

Contact qualified electrician

Tripped Thermal Circuit Breaker

See above

LEDs ‘operation’ and ‘alarm’ blink,
buzzer sounds 1/2 secs. UPS does
not start.

P (phase) and N (neutral) are
reversed at the UPS input in a
system with grounded Neutral.

In a system with grounded Neutral:
reverse the mains plug.
In other systems: disable the
indication. See 4.4.12 and 4.5.
In case of doubt contact a qualified
electrician.

UPS switched off automatically

UPS overtemperature

Allow UPS to cool down

Mains failure, battery discharged

Wait until mains returns

Programmed shutdown in progress

See 4.4.10

The load is < 5% of the max. load
and no mains power is present.
(No-load shutdown function is active,
see 4.3.2)

Wait until mains returns

LEDs ‘alarm’ and ‘on battery’ blink,
buzzer sounds 1/5 secs

Battery test just after installation or
mains failure

Allow the UPS to recharge the
batteries

Battery test shows weak battery

Have the batteries replaced